eBuild Approved Plan Set Download

17-07602-01 - Summit Creek Church - 275 W 5TH AVE

Approved Files

The files listed below are the approved plan set for this project as of the date of the last approval notice: August 6, 2018.

Using the Download Selected option will download the documents in zip files if multiple documents are selected. If more than 100 documents are selected, you'll receive multiple zip files. Please verify you have downloaded all documents you selected. Archive sets are provided in ZIP file format to make downloading large groups of files more convenient. One or more archive files is created for the plans approved at each decision.

Selected Document Date Approved Approval Type
001-site-plan.pdf 03/21/2018 SI
002-fire-exit-code.pdf 06/20/2018 SI
003-existing-demo.pdf 12/13/2017 Initial
004-floor-plan.pdf 08/06/2018 SI
005-east-sections.pdf 12/13/2017 Initial
006-north-south-sections.pdf 12/13/2017 Initial
007-cloud-framing.pdf 12/13/2017 Initial
008-details.pdf 12/13/2017 Initial
009-lav-plans-ada.pdf 12/13/2017 Initial
010-electrical.pdf 12/13/2017 Initial
011-plumbing.pdf 12/13/2017 Initial
012_M0.0.pdf 01/26/2018 Deferred
013_M0.1.pdf 01/26/2018 Deferred
014_M1.0.pdf 12/13/2017 Initial
015_M1.1.pdf 12/13/2017 Initial
016_M2.0.pdf 01/26/2018 Deferred
017_M2.1.pdf 01/26/2018 Deferred
018_M3.0.pdf 01/26/2018 Deferred
comcheck-summitcreek-electrical.pdf 12/13/2017 Initial
i3-Series_DataSheet_A05-0318.pdf 01/12/2018 Deferred
L-Series_Hrns_Strbs_HrnStrbs_Wall_DataSheet_AVDS865.pdf 01/12/2018 Deferred
Mech_comcheck.pdf 12/13/2017 Initial
Plan Review Response Letter - Summit Church.pdf 12/13/2017 Initial
platform-framing.pdf 12/13/2017 Initial
SK 5208 Cutsheet.pdf 01/12/2018 Deferred
Storefront Shops.pdf 03/02/2018 Deferred
storefront-shops.pdf 03/02/2018 Deferred
structural-revised.pdf 01/26/2018 Deferred
Summit Church1.pdf 01/12/2018 Deferred
Summit Church2.pdf 01/12/2018 Deferred
Summit Church3.pdf 01/12/2018 Deferred
Summit Creek Church Mechanical.pdf 02/02/2018 SI
SUMMIT CREEK SUBMITTAL FP.1.pdf 02/21/2018 Deferred
Summit-PC Review.pdf 12/13/2017 Initial
Supplemental Calculations for Summit Creek Church Mechanical.pdf 01/26/2018 Deferred

0 files selected

Archive Sets

Archive Date Approved Type
ApprovedPlanFiles-17-07602-01-Initial-2017-12-13T18-00-16-v01.zip 12/13/2017 Initial
ApprovedPlanFiles-17-07602-01-Initial-2017-12-13T18-00-16-v02.zip 12/13/2017 Initial
ApprovedPlanFiles-17-07602-01-Deferred-2018-01-12T10-40-35.zip 01/12/2018 Deferred
ApprovedPlanFiles-17-07602-01-Deferred-2018-01-26T11-46-54.zip 01/26/2018 Deferred
ApprovedPlanFiles-17-07602-01-SI-2018-02-02T15-55-19.zip 02/02/2018 SI
ApprovedPlanFiles-17-07602-01-Deferred-2018-02-21T16-17-25.zip 02/21/2018 Deferred
ApprovedPlanFiles-17-07602-01-Deferred-2018-03-02T13-37-09.zip 03/02/2018 Deferred
ApprovedPlanFiles-17-07602-01-SI-2018-03-21T13-00-15-v01.zip 03/21/2018 SI
ApprovedPlanFiles-17-07602-01-SI-2018-06-20T12-23-02.zip 06/20/2018 SI
ApprovedPlanFiles-17-07602-01-SI-2018-08-06T10-14-47.zip 08/06/2018 SI

Project Attachments

Attachments are provided for informational purposes.

There are no attachments for this project.

Project Requirements

PDF Copy Requirements do not need to be addressed before permits are issued. However, the inspectors will check that all requirements have been met before approving the final inspection.

ID Type Document Comment
R-A2 Architectural 002-fire-exit-code.pdf EMERGENCY EGRESS LIGHTING REQUIRED Per 2014 OSSC 1006.1 the means of egress, including the exit discharge, shall be illuminated at all times the building is occupied. Per 1006.3 an emergency electrical power system is required. The illumination levels are to be at levels specified by 1006.2/1006.3.1 with the performance of the system to be field inspected. Per 1011, the exit sign layout must be visible from all directions and indicate the direction of egress.
R-A3 Architectural 004-floor-plan.pdf Except as indicated in Section 2406.3.1 each pane of safety glazing installed in hazardous locations (2406.4) shall be identified by a manufacturer's designation specifying who applied the designation, the manufacturer or installer and the safety glazing standard with which it complies as well as the information specified in Section 2403.1. The designation shall be acid etched, sand blasted, ceramic fired, laser etched, embossed or of a type that once applied, cannot be removed without being destroyed. A label as defined in Section 202 and meeting the requirements of this section shall be permitted in lieu of the manufacturer's designation. (2014 OSSC 2406.3)
R-A4 Architectural 004-floor-plan.pdf 2014 OSSC 1008.1.9.1 Hardware: Door handles, pulls, latches, locks and other operating devices on doors required to be accessible by Chapter 11 shall not require tight grasping, tight pinching or twisting of the wrist to operate.
R-A5 Architectural 004-floor-plan.pdf Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 2014 OSSC 1008.1.9
R-A6 Architectural 004-floor-plan.pdf 2014 OSSC 1008.1.9.5 Unlatching: The unlatching of any door or leaf shall not require more than one operation.
R-A7 Architectural 002-fire-exit-code.pdf Doors serving rooms or spaces with an occupant load of 50 or more in Group A occupancy shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. (2014 OSSC 1008.1.10) All door hardware to comply with 2014 OSSC 1008.1.9
R-A8 Architectural 005-east-sections.pdf Fireblocking shall be provided in concealed spaces of stud walls and partitions, including furred spaces, and parallel rows of studs or staggered studs, as follows: 1. Vertically at the ceiling and floor levels. 2. Horizontally at intervals not exceeding 10 feet. 2014 OSSC 718.2.2
R-A9 Architectural 009-lav-plans-ada.pdf Walls and partitions within 2 feet of service sinks, urinals and water closets shall have a smooth, hard, non absorbent surface, to a height of not less than 4 feet above the floor, and except for the structural elements, the materials used in such walls shall be of a type that is not adversely affected by moisture. 2014 OSSC 1210.2.2
R-A10 Architectural 010-electrical.pdf Per AOR exit signage is existing in the Kids assembly area and shall be field verified. 2014 OSSC 1011.1
R-A11 Architectural 001-site-plan.pdf Per OAR 918-050-0170 Statewide Fee Methodology for Deferred Submittals : A fee charged for processing and reviewing deferred plan submittals shall be based on the value of the particular deferred portion or portions of the project, with a set minimum fee. This fee is in addition to the project plan review fee based on the total project value. For the COE, this fee is determined to be an amount equal to 35% of the building permit fee calculated on the specific value of each deferred submittal item of the project, with a minimum fee of $192.00 for commercial . Please provide the valuation for all deferred submittal work/items when they are submitted.
R-A12 Architectural 002-fire-exit-code.pdf Deferred Submittal : : Manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed in Group A occupancies where the occupant load due to the assembly occupancy is 300 or more. 2014 OSSC 907.2.1
R-A13 Architectural 002-fire-exit-code.pdf Kids area and Nursery area are used only when the parents/guardians are present, i.e. attending church services. 2014 OSSC 308.6.2
R-A14 Architectural 010-electrical.pdf Deferred Submittal : : Emergency egress lighting for entire rooms with non-fixed seating (kids area, auditorium), exit hallway from auditorium, lobby exits, exterior landing at required exits. 2014 OSSC 1006.1. GEC
R-A19 Architectural storefront-shops.pdf Except as indicated in Section 2406.3.1 each pane of safety glazing installed in hazardous locations (2406.4) shall be identified by a manufacturer's designation specifying who applied the designation, the manufacturer or installer and the safety glazing standard with which it complies as well as the information specified in Section 2403.1. The designation shall be acid etched, sand blasted, ceramic fired, laser etched, embossed or of a type that once applied, cannot be removed without being destroyed. A label as defined in Section 202 and meeting the requirements of this section shall be permitted in lieu of the manufacturer's designation. (2014 OSSC 2406.3)
R-A20 Architectural storefront-shops.pdf 2014 OSSC 1008.1.9.5 Unlatching: The unlatching of any door or leaf shall not require more than one operation.
R-A21 Architectural storefront-shops.pdf Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. 2014 OSSC 1008.1.9
R-EN2 Energy 008-details.pdf r-21 insulation at new interior auditorium partitions as these walls enclose a new conditioned space which was not previously conditioned. 2014 OEESC 502.1.1
R-F1 Fire Protection 001-site-plan.pdf *The fire alarm system shall be designed to OFC 907 and NFPA 72 standards. Shop drawings with equipment cut sheets, battery calcs and voltage drop calcs shall be submitted and approved prior to installation of the fire alarm system. OFC 901.2, OFC 907.1
R-F2 Fire Protection 001-site-plan.pdf *The address shall be provided on the building in a location which is plainly visible from the street, of contrasting color, a minimum of 4 inches in height. OFC 505.1
R-F3 Fire Protection 001-site-plan.pdf *Sprinkler changes of less than 15 heads or additions of less than 10 heads do not require a plan submittal but must comply with nationally recognized standards. The modifications are cumulative and all modifications on all floors are considered in the 15 head limit. Provide basic as-built plans, a service report, and sprinkler certification form at the time of final inspection. If 15 or more heads modified or more than 10 added then a complete fire sprinkler submittal is required. Any sprinkler heads that are damaged or painted are required to be replaced with new sprinkler heads. Sprinklers on the project shall be quick response for the change to light hazard OFC 901.2
R-F4 Fire Protection 001-site-plan.pdf *Submit emergency plans as per OFC 404 through 408 for Fire Marshal's review and approval prior to Final Fire inspection. Plans are required for A, E, H, I, R (university/college bldgs), SR, high-rise buildings, atriums, and some M occupancies. OFC 404 Emergency Planning and Preparedness guide (PDF) can be downloaded from http://www.eugene-or.gov/index.aspx?NID=341
R-F5 Fire Protection 001-site-plan.pdf * Per 1028.12 of the OFC the seats in the assembly space shall be fastened together in groups of not less than 3 or be fixed to the floor
R-F6 Fire Protection 001-site-plan.pdf *Supra Brand is the only approved lock box. The lock box may be purchased locally at National Fire Fighter Corporation, Omlid and Swinney or the Supra Company in Salem at 1-800-547-0252. OFC 506.1
R-F7 Fire Protection SUMMIT CREEK SUBMITTAL FP.1.pdf Return bends are required from dry systems per 7.2.2(3) NFPA 13. It looks like the line diagram detail shows this so this is just a note
R-M1 Mechanical 012_M0.0.pdf Equipment and appliances shall be installed as required by the terms of their approval, in accordance with the conditions of the listing, the manufacturer’s installation instructions and this code. Manufacturer’s installation instructions shall be available on the job site at the time of inspection. 2014 OMSC 304.1
R-M2 Mechanical 017_M2.1.pdf When duct work is located outside the building a minimum R-8 value is required. 2014 OEESC 503.2.7
R-M3 Mechanical 012_M0.0.pdf Balance report to be on site for Inspector. 2014 OMSC 403.1, 102.4
R-S2 Structural Summit Creek Church Mechanical.pdf SPECIAL INSPECTION FOR POST INSTALLED EPOXY/EXPANSION/SCREW-TYPE ANCHORS IS REQUIRED IN ACCORDANCE WITH LATEST CODE APPROVAL REPORT. (OSSC 1705)

Required Deferred Submittals

PDF Copy Per OSSC 107.3.4.2, deferred submittals are defined as those portions of the design that are not submitted at the time of the application and that are to be submitted to the building official within a specified period.

ID Type Status Status Date Details
DS-1 Other (Building) Approved 01/26/2018
CEEDGEC
010518 mechanical plans do not appear to match new rtu layout. plan check letter with this outstanding item sent. GEC Framing to support roof top mechanical equipment and mechanical equipment anchorage to structure.
DS-2 Fire Alarm System Approved 01/12/2018
CEFDKAH
Manual fire alarm system that activates the occupant notification system in accordance with Section 907.5 shall be installed din Group A occupancies where the occupant load due to the assembly occupancy is 300 or more. 2014 OSSC 907.2.1. GEC
DS-3 Other (Building) Approved 03/02/2018
CEEDGEC
PSI 022018 GEC PSI 020718. GEC Manufacturer's specifications of storefront system including how the system is anchored to structure at top and bottom. 2014 OSSC 107.2.1, 2406.4.2, 2406.4.3
DS-4 Other (Building) Approved 02/28/2018
CEEDGEC
022818 Per AOR, emergency egress lighting and code requirements shown on sheet 002 fire-exit-code. GEC Emergency egress lighting for entire rooms with non-fixed seating (kids area, lobby, auditorium), exit hallway from auditorium, lobby exits, exterior landing at required exits. 2014 OSSC 1006.1. GEC
DS-5 Fire Sprinkler System Approved 02/21/2018
CEFDATB
Deferred: DS-5 1st review Fire Sprinkler PSI013018